Difference between revisions of "FixmeBus"
From Fixme.ch
(→Overview) |
(→Overview) |
||
Line 6: | Line 6: | ||
FixmeBus is a field bus based on the half duplex [http://en.wikipedia.org/wiki/RS-485 RS485] famous hardware protocol. It is a master / slave architecture, with every slave chained together. | FixmeBus is a field bus based on the half duplex [http://en.wikipedia.org/wiki/RS-485 RS485] famous hardware protocol. It is a master / slave architecture, with every slave chained together. | ||
− | The communication protocol has following parameters: | + | The communication protocol is a standard UART, which has these following parameters: |
*38,400 bauds | *38,400 bauds |
Revision as of 00:43, 13 April 2014
Contents
Overview
FixmeBus is a field bus based on the half duplex RS485 famous hardware protocol. It is a master / slave architecture, with every slave chained together.
The communication protocol is a standard UART, which has these following parameters:
- 38,400 bauds
- 8 data bits
- 1 start and 1 stop bit
- no parity
- no flow control
Each end of the bus is terminated with a 1% 120R resistor.
Every data frame on the bus is like this (byte on the left = first byte):
- 2 bytes of slave adress (ID_HIGH and ID_LOW) => 65536 slave adress
- ID = 0 => Master
- ID = 65535 => order to all slaves (no ack)
- ID = 65000 to 65499 => order to a group of slave (no ack)
- ID = 1000 to 64999 => order to an unique slave (ack)
- 2 bytes for the function (FCT_HIGH and FCT_LOW)
- 1 byte for the number of data bytes to transmit (N_BYTE)
- n byte(s) of data (DATA) bytes (max. 200 bytes per frame)
- 2 bytes for the CRC (CRC_HIGH and CRC_LOW)
b0 | b1 | b2 | b3 | b4 | b5 | ... | bn+4 | bn+5 | bn+6 |
ID_HIGH | ID_LOW | FCT_HIGH | FCT_LOW | N_BYTE | DATA[0] | ... | DATA[n-1] | CRC_HIGH | CRC_LOW |
---|